Work

Maintenance

MS
Certificates

Certificate CERT-00471

Fail

AS 1851:2012 Routine service of fire protection systems and equipment

Tallowood Education Facilities Tallowood College, pump room, 40 University Dr, St Lucia QLD 4067

Tested
17/07/2026
Tech
Ben Kowalski
Agreement
None, billed per Job

Issued

Signed by Ben Kowalski, issued 19/07/2026

Assets tested

AssetMake and modelPositionResultFinding
FIP-01 Fire panelAmpac FireFinder PlusFire control roomPassAll zones and outputs tested, batteries within limits.
SVS-01 Sprinkler valve setViking J-1 Alarm CheckBasementFailSupervisory switch did not initiate on valve closure. Adjust and retest.

2 Assets tested, 1 failed. The Certificate fails if any Asset fails.